Potential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses
Loading...
Date
Authors
Ferreyra, Diego M.
Szwarc, Gerardo D.
Sarmiento, Ana C.
Journal Title
Journal ISSN
Volume Title
Publisher
IEEE, Institute of Electrical and Electronics Engineers
Abstract
In this work, daily energy losses were calculated for a 13,2/0,4 kV/kV, Dy11, 50 Hz, 100-kVA distribution transformer using three different load profiles based on real measurements. One of the profiles was also applied to a 400-kVA transformer. The calculations were performed for a traditional transformer as per Argentinian standard IRAM 2250 and for two high-efficiency versions, their losses being proposed based on feasible literature alternatives. High efficiency version 1 for each transformer features lower no-load losses and the same total losses; in version 2, both no-load and load losses are reduced. The apparent and active power measurements were made on a university campus with a focus on evening classes; on a company with mixed manufacturing and commercial activities; and on a continuous operation manufacturing plant. The results provide a hint as to the actual savings on transformer energy losses for such realistic daily load profiles, which is key to orient further studies regarding the incorporation of high-efficiency distribution transformers in the Argentinian market.
Description
Citation
Ferreyra, D. M.; Szwarc, G. D.; Sarmiento, A. C., "Potential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses," 2024 IEEE URUCON, Montevideo, Uruguay, 2024, pp. 1-4, doi: 10.1109/URUCON63440.2024.10850457