Potential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses

dc.coverage.spatialInternacional
dc.creatorFerreryra, Diego M.
dc.creatorSzwarc, Gerardo D.
dc.creatorSarmiento, Ana C.
dc.creator.orcid0000-0003-2251-2819
dc.creator.orcid0009-0006-2305-8442
dc.date.accessioned2025-04-04T18:35:07Z
dc.date.issued2025-01-31
dc.description.abstractIn this work, daily energy losses were calculated for a 13,2/0,4 kV/kV, Dy11, 50 Hz, 100-kVA distribution transformer using three different load profiles based on real measurements. One of the profiles was also applied to a 400-kVA transformer. The calculations were performed for a traditional transformer as per Argentinian standard IRAM 2250 and for two high-efficiency versions, their losses being proposed based on feasible literature alternatives. High efficiency version 1 for each transformer features lower no-load losses and the same total losses; in version 2, both no-load and load losses are reduced. The apparent and active power measurements were made on a university campus with a focus on evening classes; on a company with mixed manufacturing and commercial activities; and on a continuous operation manufacturing plant. The results provide a hint as to the actual savings on transformer energy losses for such realistic daily load profiles, which is key to orient further studies regarding the incorporation of high-efficiency distribution transformers in the Argentinian market.
dc.description.affiliationFil: Ferreyra, Diego Martín. Universidad Tecnológica Nacional. Facultad Regional San Francisco; Argentina.
dc.description.affiliationFil: Szwarc, Gerardo Daniel. Universidad Tecnológica Nacional. Facultad Regional San Francisco; Argentina.
dc.description.affiliationFil: Sarmiento, Ana Carina. Universidad Tecnológica Nacional. Facultad Regional San Francisco; Argentina.
dc.description.sponsorshipUniversidad Tecnológica Nacional: PID ENTCSF0010250
dc.formatpdf
dc.identifier.citationFerreyra, D. M.; Szwarc, G. D.; Sarmiento, A. C., "Potential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses," 2024 IEEE URUCON, Montevideo, Uruguay, 2024, pp. 1-4, doi: 10.1109/URUCON63440.2024.10850457
dc.identifier.doi10.1109/URUCON63440.2024.10850457
dc.identifier.otherhttps://ieeexplore.ieee.org/document/10850457
dc.identifier.urihttps://hdl.handle.net/20.500.12272/12624
dc.language.isoen_US
dc.publisherIEEE, Institute of Electrical and Electronics Engineers
dc.relation.projectidPID UTN ENTCSF0010250
dc.rightsinfo:eu-repo/semantics/embargoedAccess
dc.rights.use.
dc.source2024 IEEE URUCON, Montevideo, Uruguay, 2024, pp. 1-4
dc.subjectDistribution transformers
dc.subjectLoad losses
dc.subjectNo-load losses
dc.subjectHigh efficiency
dc.subjectDaily load profile
dc.titlePotential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses
dc.typeinfo:eu-repo/semantics/conferenceObject
dc.type.versionpublisherVersion

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
Carátula Potential Energy Savings for Three Daily Load Profiles Through Reduced Distribution Transformer Losses.pdf
Size:
136.43 KB
Format:
Adobe Portable Document Format
Description:
Artículo Principal y Único

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
3.63 KB
Format:
Item-specific license agreed upon to submission
Description: